7 MODBUS COMMUNICATIONS
7.2 MODBUS FUNCTIONS
7
7.2.7 FUNCTION CODE 08 – LOOPBACK TEST
Modbus Implementation: Loopback Test
PQM Implementation: Loopback Test
This function is used to test the integrity of the communication link. The PQM will echo the request.
MESSAGE FORMAT AND EXAMPLE:
Loopback test from slave 11.
Table 7–6: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 08H
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
08
loopback test
DIAG CODE
2
00 00
must be 00 00
DATA
2
00 00
must be 00 00
CRC
2
E0 0B
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message from slave 17
FUNCTION CODE
1
08
loopback test
DIAG CODE
2
00 00
must be 00 00
DATA
2
00 00
must be 00 00
CRC
2
E0 0B
CRC error code
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...