GE Power Management
PQM Power Quality Meter
4-55
4 PROGRAMMING
4.6 S5 TESTING
4
4.6.2 CURRENT/VOLTAGE SIMULATION
Figure 4–35: SETPOINTS PAGE 5 – TESTING / CURRENT/VOLTAGE SIMULATION
Simulated currents and voltages can be forced instead of the actual currents or voltages sensed by the exter-
nal CTs and VTs. This allows for verification of all current and voltage related relay functions.
•
SIMULATION: Enter
ON
to switch from actual currents and voltages to the programmed simulated values.
Set this setpoint
OFF
after simulation is complete.
•
SIMULATION ENABLED FOR: Select the desired length of time that simulation will be enabled. When the
programmed time has elapsed, current and voltage simulation will turn off. If unlimited is selected, simu-
lated currents and voltages will be used until simulation is turned off via the simulation on/off message or
via the serial port or until control power is removed from the PQM.
•
PHASE A/B/C/NEUTRAL CURRENT: Enter the desired phase and neutral currents for simulation.
•
Vax/Vbx/Vcx VOLTAGE: Enter the desired voltages for simulation. The voltages entered will be line or
phase quantities depending upon the VT wiring type selected with the
S2 SYSTEM SETUP \ CURRENT/
VOLTAGE CONFIGURATION \ VT WIRING
setpoint.
•
PHASE ANGLE: The phase angle in this setpoint represents the phase shift from a unity power factor.
Enter the desired phase angle between the current and voltage. The angle between the individual currents
and voltages is fixed at 120°.
]] SETPOINTS
]] S5 TESTING
] CURRENT/VOLTAGE
] SIMULATION
SIMULATION:
OFF
SIMULATION ENABLED
FOR: 15 min
PHASE A CURRENT:
0 A
]] SETPOINTS
]] S1 PQM SETUP
SETPOINT
Range: OFF, ON
Range: 5 to 300, UNLIMITED
Step: 5 min
PHASE B CURRENT:
0 A
NEUTRAL CURRENT:
0 A
Vax VOLTAGE:
0 V
] TEST RELAYS & LEDS
]
Range: 0 to 1000; Step 1 A
Range: 0 to 65000, Step 1 V
Vbx VOLTAGE:
0 V
Vcx VOLTAGE:
0 V
PHASE ANGLE:
0 DEGREES
Range: 0 to 1000; Step 1 A
Range: 0 to 1000; Step 1 A
Range: 0 to 65000, Step 1 V
Range: 0 to 65000, Step 1 V
Range: 0 to 359, Step: 1°
M E S S A G E
M E S S A G E
M E S S A G E
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...