GE Power Management
PQM Power Quality Meter
7-43
7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
ANALOG
OUTPUT 2
continued
106D
Analog Output 2 Alternate Max Value
See Analog Output Range Table on page 7–63
0
106E
Reserved
106F
Analog Output 2 Serial Value
1
---
F2
0
ANALOG
OUTPUT 3
1070
Analog Output 3 Main Type
0 to 59
1
---
F14
0=NOT USED
1071
Analog Output 3 Main Min Value
See Analog Output Range Table on page 7–63
1072
Analog Output 3 Main Max Value
See Analog Output Range Table on page 7–63
1073
Analog Output 3 Alternate Type
0 to 59
1
---
F14
0=NOT USED
1074
Analog Output 3 Alternate Min Value
See Analog Output Range Table on page 7–63
1075
Analog Output 3 Alternate Max Value
See Analog Output Range Table on page 7–63
1076
Reserved
1077
Analog Output 3 Serial Value
1
---
F2
0
ANALOG
OUTPUT 4
1078
Analog Output 4 Main Type
0 to 59
1
---
F14
0=NOT USED
1079
Analog Output 4 Main Min Value
See Analog Output Range Table on page 7–63
107A
Analog Output 4 Main Max Value
See Analog Output Range Table on page 7–63
107B
Analog Output 4 Alternate Type
0 to 59
1
---
F14
0=NOT USED
107C
Analog Output 4 Alternate Min Value
See Analog Output Range Table on page 7–63
107D
Analog Output 4 Alternate Max Value
See Analog Output Range Table on page 7–63
107E
Reserved
107F
Analog Output 4 Serial Value
1
---
F2
0
ANALOG
INPUT
1080
Analog Input Main/Alt Select Relay
0 to 3
1
---
F19
0=OFF
1081
Analog In Main Name 1
st
and 2
nd
char.
---
---
ASCII
F10
““
1082
Analog In Main Name 3
rd
and 4
th
char.
---
---
ASCII
F10
“MA”
1083
Analog In Main Name 5
th
and 6
th
char.
---
---
ASCII
F10
“IN”
1084
Analog In Main Name 7
th
and 8
th
char.
---
---
ASCII
F10
“ A”
1085
Analog In Main Name 9
th
and 10
th
char.
--
--
ASCII
F10
“NA”
1086
Analog In Main Name 11
th
and 12
th
char.
--
--
ASCII
F10
“LO”
1087
Analog In Main Name 13
th
and 14
th
char.
---
---
ASCII
F10
“G “
1088
Analog In Main Name 15
h
and 16
th
char.
----
----
ASCII
F10
“IN”
1089
Analog In Main Name 17
th
and 18
th
char.
---
---
ASCII
F10
“PU”
108A
Analog In Main Name 19
th
and 20
th
char.
---
---
ASCII
F10
“T “
108B
Analog In Main Units 1
st
and 2
nd
char.
---
---
ASCII
F10
“ U”
108C
Analog In Main Units 3
rd
and 4
th
char.
---
---
ASCII
F10
“ni”
108D
Analog In Main Units 5
th
and 6
th
char.
---
---
ASCII
F10
“ts”
108E
Analog In Main Units 7
th
and 8
th
char.
---
---
ASCII
F10
“”
108F
Analog In Main Units 9
th
and 10
th
char.
---
---
ASCII
F10
““
1090
Analog Input Main 4 mA Value
0 to 65000
1
---
F1
0
1091
Analog Input Main 20 mA Value
0 to 65000
1
---
F1
0
1092
Analog Input Main Relay
0 to 4
1
---
F29
0=OFF
1093
Analog Input Main Level
0 to 65000
1
---
F1
0
1094
Analog Input Main Delay
5 to 6000
5
0.1 xs
F1
100=10.0 s
1095
Reserved
1096
Reserved
1097
Reserved
1098
Analog In Alt Name 1
st
and 2
nd
char.
---
---
ASCII
F10
““
Table 7–10: PQM MEMORY MAP (Sheet 29 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...