GE Power Management
PQM Power Quality Meter
4-47
4 PROGRAMMING
4.5 S4 ALARMS/CONTROL
4
•
POWER FACTOR LEAD 1 / 2 RELAY: Power factor detection can either be disabled, used as an alarm or
as a process control. Set this setpoint to off if the feature is not required. Selecting alarm relay will cause
the alarm relay to activate and display an alarm message when the power factor is more leading than the
level set. Selecting AUX1, AUX2 or AUX3 relay will cause the respective auxiliary relay to activate when
the power factor is equal to or more leading than the level set, but no message will be displayed. This is
intended for process control. A minimum of 20V applied must exist on all voltage inputs before this feature
will operate.
•
POWER FACTOR LEAD 1 / 2 PICKUP: When a leading power factor equals or exceeds the level set by
this setpoint, a power factor lead 1/2 condition will occur.
•
POWER FACTOR LEAD 1 / 2 DROPOUT: When a leading power factor drops below the level set by this
setpoint, the power factor lead 1/2 condition will drop out.
•
POWER FACTOR LEAD 1 / 2 DELAY: If the power factor equals or exceeds the
POWER FACTOR LEAD 1/2
PICKUP
setpoint value and remains this way for the time delay programmed in this setpoint, a power factor
lead 1/2 condition will occur.
This setpoint also applies to the
POWER FACTOR DROPOUT 1/2
setpoint. If the power factor drops below the
POWER FACTOR LEAD 1/2 DROPOUT
setpoint value and remains this way for the time delay programmed in
this setpoint, the power factor lead 1/2 condition will drop out. If the
POWER FACTOR LEAD 1/2 RELAY
setpoint
is set to
ALARM
, the alarm relay will deactivate and the
POWER FACTOR LEAD 1/2 ALARM
message will be
cleared. If the
POWER FACTOR LEAD 1/2 RELAY
setpoint is set to
AUX1
,
AUX2
, or
AUX3
, the respective auxiliary
relay will deactivate.
•
POWER FACTOR LAG 1 / 2 RELAY: Power factor detection can either be disabled, used as an alarm or
as a process control. Set this setpoint to off if the feature is not required. Selecting alarm relay will cause
the alarm relay to activate and display an alarm message when the power factor is more lagging than the
level set. Selecting
AUX1
,
AUX2
, or
AUX3
relay activates the respective auxiliary relay when the power factor
is equal to or more lagging than the level set, but no message will be displayed. This is intended for pro-
cess control. A minimum of 20 V applied must exist on all voltage inputs before this feature will operate.
•
POWER FACTOR LAG 1 / 2 PICKUP: When a lagging power factor equals or exceeds the level set by this
setpoint, a power factor lag 1/2 condition will occur.
•
POWER FACTOR LAG 1 / 2 DROPOUT: When a lagging power factor drops below the level set by this
setpoint, the power factor lag 1/2 condition will drop out.
•
POWER FACTOR LAG 1 / 2 DELAY: If the power factor equals or exceeds the
POWER FACTOR LAG 1/2
PICKUP
setpoint value and remains this way for the time delay programmed in this setpoint, a power factor
lag 1/2 condition will occur.
This setpoint also applies to the
POWER FACTOR LAG 1/2 DROPOUT
setpoint. If the power factor drops below
the
POWER FACTOR LAG 1/2 DROPOUT
setpoint value and remains this way for the time delay programmed in
this setpoint, the power factor 1/2 lag condition will drop out. If the
POWER FACTOR LAG 1/2 RELAY
setpoint is
set to
ALARM
, the alarm relay will deactivate and the
POWER FACTOR LAG 1/2 ALARM
message will be
cleared. If the
POWER FACTOR LAG 1/2 RELAY
setpoint is set to
AUX1
,
AUX2
. or
AUX3
, the respective auxiliary
relay will deactivate.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...