4-44
PQM Power Quality Meter
GE Power Management
4.5 S4 ALARMS/CONTROL
4 PROGRAMMING
4
•
POSITIVE REAL POWER RELAY: Positive real power level detection can either be disabled, used as an
alarm or as a process control. Set this setpoint to off if the feature is not required. Selecting alarm relay will
cause the alarm relay to activate and display an alarm message whenever a positive real power level
exceeds the selected level. Selecting auxiliary relay will cause the auxiliary relay to activate for a set level
of positive real power but no message will be displayed. This is intended for process control.
•
POSITIVE REAL POWER LEVEL: When the three phase real power equals or exceeds the level set by
this setpoint, an excess positive real power condition will occur.
•
POSITIVE REAL POWER DELAY: If the positive real power equals or exceeds the
POSITIVE REAL POWER
LEVEL
setpoint value for the time delay programmed in this setpoint, an excessive positive real power con-
dition will occur.
•
NEGATIVE REAL POWER RELAY: Negative real power level detection can either be disabled, used as
an alarm or as a process control. Set this setpoint to off if the feature is not required. Selecting alarm relay
will cause the alarm relay to activate and display an alarm message whenever a negative real power level
exceeds the selected level. Selecting auxiliary relay will cause the auxiliary relay to activate for a set level
of negative real power but no message will be displayed. This is intended for process control.
•
NEGATIVE REAL POWER LEVEL: When the three phase real power equals or exceeds the level set by
this setpoint, an excess negative real power condition will occur.
•
NEGATIVE REAL POWER DELAY: If the negative real power equals or exceeds the
NEGATIVE REAL
POWER LEVEL
setpoint value for the time delay programmed in this setpoint, an excessive negative real
power condition will occur.
•
POSITIVE REACTIVE POWER RELAY: Positive reactive power level detection can either be disabled,
used as an alarm or as a process control. Set this setpoint to off if the feature is not required. Selecting
alarm relay will cause the alarm relay to activate and display an alarm message whenever a positive reac-
tive power level exceeds the selected level. Selecting auxiliary relay will cause the auxiliary relay to acti-
vate for a set level of positive reactive power but no message will be displayed. This is intended for
process control.
•
POSITIVE REACTIVE POWER LEVEL: When the three phase reactive power equals or exceeds the level
set by this setpoint, an excess positive reactive power condition will occur.
•
POSITIVE REACTIVE POWER DELAY: If the positive reactive power equals or exceeds the
POSITIVE
REACTIVE POWER LEVEL
setpoint value for the time delay programmed in this setpoint, an excessive positive
reactive power condition will occur.
•
NEGATIVE REACTIVE POWER RELAY: Negative reactive power level detection can either be disabled,
used as an alarm or as a process control. Set this setpoint to off if the feature is not required. Selecting
alarm relay will cause the alarm relay to activate and display an alarm message whenever a negative reac-
tive power level exceeds the selected level. Selecting auxiliary relay will cause the auxiliary relay to acti-
vate for a set level of negative reactive power but no message will be displayed. This is intended for
process control.
•
NEGATIVE REACTIVE POWER LEVEL: When the three phase reactive power equals or exceeds the
level set by this setpoint, an excess negative reactive power condition will occur.
•
NEGATIVE REACTIVE POWER DELAY: If the negative reactive power equals or exceeds the
NEGATIVE
REACTIVE POWER LEVEL
setpoint value for the time delay programmed in this setpoint, an excessive nega-
tive reactive power condition will occur.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...