GE Power Management
PQM Power Quality Meter
7-7
7 MODBUS COMMUNICATIONS
7.2 MODBUS FUNCTIONS
7
7.2.5 FUNCTION CODE 06 – STORE SINGLE SETPOINT
Modbus Implementation: Preset Single Register
PQM Implementation: Store Single Setpoint
This command allows the master to store a single setpoint into the memory of a PQM. The slave response to
this function code is to echo the entire master transmission.
MESSAGE FORMAT AND EXAMPLE:
Request slave 11 to store the value 01E4 in setpoint address 1020. After the transmission in this example is
complete, setpoint address 1020 will contain the value 01F4.
Table 7–4: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 06H
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
06
store single setpoint
DATA STARTING ADDRESS
2
10 20
setpoint address 1020
DATA
2
01 E4
data for setpoint address 1020
CRC
2
8E 47
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message from slave 17
FUNCTION CODE
1
06
store single setpoint
DATA STARTING ADDRESS
2
10 20
setpoint address 1020
DATA
2
01 E4
data stored in setpoint address 1020
CRC
2
8E 47
CRC error code
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...