Reading a negative 3 Phase Real Power actual value from the PQM:
4.
Following the method described above:
DATA VALUE = (FF3A
×
2
16
) + EA7B
hexadecimal
= (65338
×
2
16
) + 60027
converted to decimal
= 4282051195
decimal
5.
The most significant bit of the High Order register is set, therefore the DATA VALUE is calculated as:
DATA VALUE = DATA VALUE – 2
32
= 4282051195 – 4294967296
= –12916101
Applying the Units & Scale parameters to the DATA VALUE, we multiply the DATA VALUE by 0.01 kW. There-
fore the resultant value of 3 Phase Real Power as read from the memory map is –129161.01 kW.
REGISTER
ACTUAL VALUE (hex)
DESCRIPTION
UNITS & SCALE
FORMAT
02F0
FF3A
3 Phase Real Power (high)
0.01 x kW
F4
02F1
EA7B
3 Phase Real Power (low)
0.01 x kW
F4
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...