7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
to
↓
↓
↓
↓
↓
↓
12CF
Reserved
TRACE
MEMORY
12D0
Trace Memory Usage
0 to 2
1
---
F37
0=1x36 cycles
12D1
Trace Memory Trigger Mode
0 to 1
1
---
F38
0=ONE SHOT
12D2
Ia Overcurrent Trigger Level
1 to 151***
1
% CT
F1
151=OFF
12D3
Ib Overcurrent Trigger Level
1 to 151***
1
% CT
F1
151=OFF
12D4
Ic Overcurrent Trigger Level
1 to 151***
1
% CT
F1
151=OFF
12D5
In Overcurrent Trigger Level
1 to 151***
% CT
F1
151=OFF
12D6
Va Overvoltage Trigger Level
20 to 151***
1
% VT
F1
151=OFF
12D7
Vb Overvoltage Trigger Level
20 to 151***
1
% VT
F1
151=OFF
12D8
Vc Overvoltage Trigger Level
20 to 151***
1
% VT
F1
151=OFF
12D9
Va Undervoltage Trigger Level
20 to 151***
1
% VT
F1
151=OFF
12DA
Vb Undervoltage Trigger Level
20 to 151***
1
% VT
F1
151=OFF
12DB
Vc Undervoltage Trigger Level
20 to 151***
1
% VT
F1
151=OFF
12DC
Switch Input A Trigger
0 to 2
1
---
F39
0=OFF
12DD
Switch Input B Trigger
0 to 2
1
---
F39
0=OFF
12DE
Switch Input C Trigger
0 to 2
1
---
F39
0=OFF
12DF
Switch Input D Trigger
0 to 2
1
---
F39
0=OFF
12E0
Trace Memory Trigger Delay
0 to 30
1
cycles
F1
0 cycles
12E1
Trace Memory Waveform Selection
0 to 6
1
---
F40
0=Ia
12E2
Trace Memory Trigger Relay
0 to 4
1
---
F29
0=OFF
12E3
Reserved
to
↓
↓
↓
↓
↓
↓
12EF
Reserved
PRODUCT
OPTIONS
12F0
Product Options Upgrade
0 to 23
1
---
F116
0
12F1
Product Modifications Upgrade MOD1
0 to 999
1
---
F1
0
12F2
Product Modifications Upgrade MOD2
0 to 999
1
---
F1
0
12F3
Product Modifications Upgrade MOD3
0 to 999
1
---
F1
0
12F4
Product Modifications Upgrade MOD4
0 to 999
1
---
F1
0
12F5
Product Modifications Upgrade MOD5
0 to 999
1
---
F1
0
12F6
Passcode Input 1
32 to 127
1
---
F10
32
12F7
Passcode Input 2
32 to 127
1
---
F10
32
12F8
Passcode Input 3
32 to 127
1
---
F10
32
12F9
Passcode Input 4
32 to 127
1
---
F10
32
12FA
Passcode Input 5
32 to 127
1
---
F10
32
12FB
Passcode Input 6
32 to 127
1
---
F10
32
12FC
Passcode Input 7
32 to 127
1
---
F10
32
12FD
Passcode Input 8
32 to 127
1
---
F10
32
12FE
Passcode Input 9
32 to 127
1
---
F10
32
12FF
Passcode Input 10
32 to 127
1
---
F10
32
1300
Reserved
to
↓
↓
↓
↓
↓
↓
131F
Reserved
Table 7–10: PQM MEMORY MAP (Sheet 40 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...