7-38
PQM Power Quality Meter
GE Power Management
7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
EVENT
RECORD
continued
0AE0
Record #N Event Number
---
---
---
F1
N/A
0AE1
Record #N Event Cause
---
---
---
F36
0 = NO EVENT
0AE2
Record #N Time - Hours/Minutes
---
---
---
F22
N/A
0AE3
Record #N Time - Seconds
---
---
---
F23
N/A
0AE4
Record #N Date - Month/Day
---
---
---
F24
N/A
0AE5
Record #N Date - Year
---
---
---
F25
N/A
0AE6
Record #N Switches and Relays States
---
---
---
F111
N/A
0AE7
Record #N Ia
---
---
A
F1
N/A
0AE8
Record #N Ib
---
---
A
F1
N/A
0AE9
Record #N Ic
---
---
A
F1
N/A
0AEA
Record #N In
---
---
A
F1
N/A
0AEB
Record #N I Unbalance
---
---
0.1 x%
F1
N/A
0AEC
Record #N Van (high)
---
---
V
F3
N/A
0AED
Record #N Van (low)
---
---
V
F3
N/A
0AEE
Record #N Vbn (high)
---
---
V
F3
N/A
0AEF
Record #N Vbn (low)
---
---
V
F3
N/A
0AF0
Record #N Vcn (high)
---
---
V
F3
N/A
0AF1
Record #N Vcn (low)
---
---
V
F3
N/A
0AF2
Record #N Vab (high)
---
---
V
F3
N/A
0AF3
Record #N Vab (low)
---
---
V
F3
N/A
0AF4
Record #N Vbc (high)
---
---
V
F3
N/A
0AF5
Record #N Vbc (low)
---
---
V
F3
N/A
0AF6
Record #N Vca (high)
---
---
V
F3
N/A
0AF7
Record #N Vca (low)
---
---
V
F3
N/A
0AF8
Record #N V Unbalance
---
---
0.1 x%
F1
N/A
0AF9
Record #N Pa (high)
---
---
0.01 x kW
F4
N/A
0AFA
Record #N Pa (low)
---
---
0.01 x kW
F4
N/A
0AFB
Record #N Qa (high)
---
---
0.01 x kvar
F4
N/A
0AFC
Record #N Qa (low)
---
---
0.01 x kvar
F4
N/A
0AFD
Record #N Sa (high)
---
---
0.01 x kVA
F3
N/A
0AFE
Record #N Sa (low)
---
---
0.01 x kVA
F3
N/A
0AFF
Record #N PFa
---
---
0.01 x PF
F2
N/A
0B00
Record #N Pb (high)
---
---
0.01 x kW
F4
N/A
0B01
Record #N Pb (low)
---
---
0.01 x kW
F4
N/A
0B02
Record #N Qb (high)
---
---
0.01 x kvar
F4
N/A
0B03
Record #N Qb (low)
---
---
0.01 x kvar
F4
N/A
0B04
Record #N Sb (high)
---
---
0.01 x kVA
F3
N/A
0B05
Record #N Sb (low)
---
---
0.01 x kVA
F3
N/A
0B06
Record #N PFb
---
---
0.01 x PF
F2
N/A
0B07
Record #N Pc (high)
---
---
0.01 x kW
F4
N/A
0B08
Record #N Pc (low)
---
---
0.01 x kW
F4
N/A
0B09
Record #N Qc (high)
---
---
0.01 x kvar
F4
N/A
0B0A
Record #N Qc (low)
---
---
0.01 x kvar
F4
N/A
0B0B
Record #N Sc (high)
---
---
0.01 x kVA
F3
N/A
Table 7–10: PQM MEMORY MAP (Sheet 24 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...