GE Power Management
PQM Power Quality Meter
4-35
4 PROGRAMMING
4.4 S3 OUTPUT RELAYS
4
4.4.2 ALARM RELAY
•
ALARM OPERATION: The terms ‘failsafe’ and ‘non-failsafe’ are defined above as implemented in the
PQM. If an alarm is required when the PQM is not operational due to a loss of control power, select failsafe
operation. Otherwise, choose non-failsafe.
•
ALARM ACTIVATION: If an alarm indication is required only while an alarm is present, select unlatched.
Once the alarm condition disappears, the alarm and associated message automatically clear. To ensure all
alarms are acknowledged, select latched. Even if an alarm condition is no longer present, the alarm relay
and message can only be cleared by pressing the
key or by sending the reset command via the
computer.
4.4.3 AUXILIARY RELAYS
•
AUXILIARY 1, 2, 3 OPERATION: The terms ‘failsafe’ and ‘non-failsafe’ are defined above as implemented
in the PQM. If an output is required when the PQM is not operational due to a loss of control power, select
failsafe auxiliary operation, otherwise, choose non-failsafe.
•
AUXILIARY 1, 2, 3 ACTIVATION: If an auxiliary relay output is required only while the selected conditions
are present, select unlatched. Once the selected condition disappears, the auxiliary relay returns to the
non-active state. To ensure all conditions are acknowledged, select latched. If the condition is no longer
present, the auxiliary relay can be reset by pressing the
key or by sending the reset command via
the computer.
Since the relays can be assigned to perform many different functions, the PQM uses a priority system
to determine which function will control the relays if they happen to be assigned to more than one
function. The Table below shows the priority of the functions.
For example, if one of the relays is assigned to an alarm function and it is also assigned to one of the pulse
output parameters, the relay will respond only to the pulse output function.
Table 4–4: AUXILIARY RELAYS ACTIVATION PRIORITY
PRIORITY
FUNCTION
HIGHEST
PULSE OUTPUT
↓
ANALOG INPUT MAIN/ALT SELECT
LOWEST
ALL ALARM FUNCTIONS
RESET
R E S E T
NOTE
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...