Chapter 6 Installing System Modules
Installation and Commissioning Manual
253
F
S
P
3000R
7 R
11
.1 8000
0015930
Issue
B
, ©
2012
ADVA AG Optical Netw
orking
ADVA Conf
idential
Procedure
Step 1
Read the installation or the cabling plan, or contact the system admin-
istrator to get relevant information you need for performing this task.
Step 2
Connect one end of the proper Ethernet cable into one of the Ethernet
ports on the NCU labeled C1 (or C2 if available), ensuring the RJ45
plug clicks into place.
Step 3
Run the cable down through the space between two fiber fingers,
route it in the fiber tray right up to the OSCM and run it up through the
space between two fiber fingers as shown in
.
Figure 74:
Example of NCU to OSCM Cable Connection
Step 4
Connect the other end of the Ethernet cable into one of the Ethernet
client ports on the OSCM labeled C1, C2 and C3, ensuring the RJ45
plug also clicks into place.
Step 5
Check the LAN port status LED indicators. See the
Maintenance and
Troubleshooting Manual
,
Chapter 7
for details.
End of Procedure
Should you have any difficulty performing this procedure, contact ADVA Optical
Networking’s
.
P
S
Note
The RJ45 plug will fit into the Ethernet ports (RJ45 receptacles) only
one way. It will click into place when properly inserted.
Ensure the release tab of the plug is pressed before pulling the plug
out.
P
S
Note
For information about how to enable transport of OSC traffic to the
local NE through an Ethernet cable, refer to the
Provisioning and
Operations Manual
,
Chapter 3
.