Rack-Mounting the DCF1HU-P Shelf
200
Installation and Commissioning Manual
F
S
P
3000R
7 R
11
.1 8000
0015930
Issue
B
, ©
2012
ADVA AG Optical Netw
orking
ADVA Conf
idential
•
The DCF1HU-P Shelf requires 1 HU (44.45 mm = 1.75 in) of space in the
rack.
It is assumed that you are familiar with ESD-prevention precautions that should
be taken to avoid ESD damage to the equipment.
Tools and Parts Required
•
4 x appropriate rack screws and washers (not delivered with the shelf). Use
screws that fit the threaded holes in your rack.
•
Appropriate screwdriver
To mount a DCF1HU-P Shelf into a rack, perform the following steps:
Procedure
Step 1
Determine where you have to mount the DCF1HU-P Shelf. Read the
installation plan or the cabling plan to get information about:
•
the shelf that is to be mounted
•
the rack, which is to hold this shelf
Step 2
On the rack mounting rails, locate and mark the mounting holes in
which the shelf has to be fixed. There should a space of 1HU between
the DCF1HU-P Shelf and the shelf above.
Step 3
If required, install two cage nuts in the corresponding holes on both
sides of the rack.
CAUTION
Only Service Personnel are allowed to mount the DCF1HU-P Shelf
into a rack or cabinet.
Ensure that you are grounded with a wrist strap or equivalent while
mounting the brackets to a shelf which contains ESD-sensitive
devices.
CAUTION
Risk of Fire and Risk of Damage to Equipment due to Overheating!
When mounting a DCF1HU-P Shelf beneath a 7HU Shelf, leave a
minimum of DCF1HU-P Shelf of space between the bottom of a 7HU
Shelf and the top of a DCF1HU-P Shelf to allow a free flow of air to
the 7HU Shelf above. Failure to do so could cause overheating
conditions and results in incorrect operation, damage to system
components or fire.
PS
Note
To complete the following steps, you may want a helper to hold the
shelf in place while you secure it to the bay.