Installing a 40CSM/2HU Shelf
184
Installation and Commissioning Manual
F
S
P
3000R
7 R
11
.1 8000
0015930
Issue
B
, ©
2012
ADVA AG Optical Netw
orking
ADVA Conf
idential
Step 4
Using the fixing screws provided, fit the appropriate ETSI bracket as
follows:
a) Insert a screw through a mounting hole in the bracket into the
threaded hole in the shelf side panel.
b) Insert a second screw through the remaining mounting hole in the
bracket into the threaded hole in the shelf side panel.
c) Tighten the screws with a Torx screwdriver TX25.
Figure 39:
ETSI Bracket Fitted to the 40CSM/2HU-#D02-#D32
Shelf
Step 5
Repeat steps 3 to 4 of this procedure for the opposite side.
End of Procedure
Fitting the 40CSM/2HU Shelf with NEBS Brackets
This subsection describes the procedure that must be followed in order to fit the
40CSM/2HU shelf with NEBS brackets.
NEBS brackets are required to adapt the 40CSM/2HU shelf to the NEBS stan-
dard rack dimensions.
CAUTION
Only Service Personnel are allowed to perform this procedure.
Ensure that you are grounded with a wrist strap or equivalent while
mounting the brackets to a shelf which contains ESD-sensitive
devices.