communication over MMS are supported. Disturbance recording file (COMTRADE)
uploading can be done over MMS or FTP.
The front port is only intended for PCM600 communication,
maintenance, training and test purposes due to risk of interference
during normal operation.
19.4.2
Communication interfaces and protocols
GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v7
Table 468:
Supported station communication interfaces and protocols
Protocol
Ethernet
Serial
100BASE-FX (ST
connector)
Glass fibre (ST connector)
EIA-485
IEC 61850–8–1
●
-
-
DNP3
●
●
●
IEC 60870-5-103
-
●
●
● = Supported
When double Ethernet ports are activated, make sure that all ports are
connected to different subnets. For example: port 1 has IP address
198.168.101.10 with subnet mask 255.255.255.0, and port 2 has IP
address 198.168.102.10 with subnet mask 255.255.255.0.
19.4.3
Settings
PID-6702-SETTINGS v3
Table 469:
IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
GOOSEPortEd1
AP_FRONT
AP_1
AP_2
AP_3
AP_4
AP_5
AP_6
-
-
AP_1
Selection of GOOSE port (only for IEC61850
Ed1)
Protocol Edition
Ed 1
Ed 2
-
-
Ed 1
Protocol Edition
Table continues on next page
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
627
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...