![ABB Relion RES670 Скачать руководство пользователя страница 224](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485224.webp)
Name
Values (Range)
Unit
Step
Default
Description
Characterist3
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 3
I2-3>
1 - 2500
%IB
1
33
Negative sequence current op level for step 3
in % of IBase
t3
0.000 - 60.000
s
0.001
0.800
Time delay of step 3 when definite time char.
is selected
TD3
0.05 - 999.00
-
0.01
0.05
Time multiplier for the step 3 selected time
characteristic
IMin3
1.00 - 10000.00
%IB
1.00
33
Minimum current for step 3
t3Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse time
characteristic step 3
MultPU3
1.0 - 10.0
-
0.1
2.0
Multiplier for scaling the current setting value
for step 3
DirModeSel4
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 4 (Disabled, Nondir,
Forward, Reverse)
Characterist4
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 4
Table continues on next page
Section 8
1MRK 511 408-UUS A
Current protection
218
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...