Name
Values (Range)
Unit
Step
Default
Description
Characterist3
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 3
Pickup3
1 - 2500
%IB
1
33
Residual current operate level for step 3 in %
of IBase
t3
0.000 - 60.000
s
0.001
0.800
Def time delay or add time delay for inverse
char of step 3
TD3
0.05 - 999.00
-
0.01
0.05
Time multiplier for the step 3 selected time
characteristic
IMin3
1.00 - 10000.00
%IB
1.00
33
Minimum operate residual current for step 3
in % of IBase
t3Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse time
characteristic step 3
MultPU3
1.0 - 10.0
-
0.1
2.0
Multiplier for the residual current setting value
for step 3
HarmBlock3
Disabled
Enabled
-
-
Enabled
Enable block of step 3 for harmonic restraint
DirModeSel4
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 4 (Off, Non-dir,
Forward, Reverse)
Table continues on next page
Section 8
1MRK 511 408-UUS A
Current protection
194
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...