![ABB Relion RES670 Скачать руководство пользователя страница 286](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485286.webp)
Voltage
Time
HystAbs1
PICKUP
TRIP
PICKUP
PICKUP 1
PICKUP
TRIP
t
tIReset1
Time
Time
Integrator
t
Frozen Timer
Linearly
decreased
Instantaneous
Measured Voltage
tIReset1
ANSI05000011-2-en.vsd
ANSI05000011 V2 EN-US
Figure 90:
Voltage profile causing a reset of the pickup signal for step 1, and inverse time delay at different
reset types
Definite timer delay
Section 9
1MRK 511 408-UUS A
Voltage protection
280
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...