Name
Values (Range)
Unit
Step
Default
Description
EnBlkLowI_UC1
Disabled
Enabled
-
-
Disabled
Enable internal low current level blocking for
UC1
BlkLowCurr_UC1
0 - 150
%IB
1
20
Internal low current blocking level for UC1 in
% of IBase
PickupCurr_UC1
2.0 - 150.0
%IB
1.0
70.0
Operate undercurrent level for UC1 in % of
IBase
tDef_UC1
0.00 - 6000.00
s
0.01
0.50
Definite time delay of UC1
tResetDef_UC1
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve UC1
HarmRestr_UC1
Disabled
Enabled
-
-
Disabled
Enable block of UC1 by 2nd harmonic
restrain
Operation_UC2
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of UC2
EnBlkLowI_UC2
Disabled
Enabled
-
-
Disabled
Enable internal low current level blocking for
UC2
BlkLowCurr_UC2
0 - 150
%IB
1
20
Internal low current blocking level for UC2 in
% of IBase
PickupCurr_UC2
2.0 - 150.0
%IB
1.0
70.0
Operate undercurrent level for UC2 in % of
IBase
tDef_UC2
0.00 - 6000.00
s
0.01
0.50
Definite time delay of UC2
HarmRestr_UC2
Disabled
Enabled
-
-
Disabled
Enable block of UC2 by 2nd harmonic
restrain
Operation_OV1
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of OV1
PickupVolt_OV1
2.0 - 200.0
%VB
0.1
150.0
Operate voltage level for OV1 in % of VBase
CurveType_OV1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
-
-
Definite time
Selection of time delay curve type for OV1
tDef_OV1
0.00 - 6000.00
s
0.01
1.00
Operate time delay in sec for definite time use
of OV1
tMin_OV1
0.00 - 6000.00
s
0.01
0.05
Minimum operate time for Inverse-Time
curves for OV1
TD_OV1
0.05 - 999.00
-
0.01
0.30
Time multiplier for the dependent time delay
for OV1
Operation_OV2
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of OV2
PickupVolt_OV2
2.0 - 200.0
%VB
0.1
150.0
Operate voltage level for OV2 in % of VBase
CurveType_OV2
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
-
-
Definite time
Selection of time delay curve type for OV2
tDef_OV2
0.00 - 6000.00
s
0.01
1.00
Operate time delay in sec for definite time use
of OV2
Table continues on next page
1MRK 511 408-UUS A
Section 11
Multipurpose protection
Phasor measurement unit RES670 2.2 ANSI
331
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...