Table 94:
OC4PTOC (51_67) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
PUMinOpPhSel
1 - 100
%IB
1
7
Minimum current for phase selection in % of
IBase
2ndHarmStab
5 - 100
%
1
20
Operate level of 2nd harmonic curr in % of
fundamental curr
I1>Min
5 - 2500
%IB
1
5
Minimum used operating phase current level
for step 1 in % of IBase, if I1> is less than
I1>Min then I1> is set to I1>Min
I1>Max
5 - 2500
%IB
1
2500
Maximum used operating phase current level
for step 1 in % of IBase, if I1> is greater than
I1>Max then I1> is set to I1>Max
ResetTypeCrv1
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for step 1
tReset1
0.000 - 60.000
s
0.001
0.020
Constant reset time for step 1
tPCrv1
0.005 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 1
tACrv1
0.005 - 200.000
-
0.001
13.500
Parameter A for customer programmable
curve for step 1
tBCrv1
0.00 - 20.00
-
0.01
0.00
Parameter B for customer programmable
curve for step 1
tCCrv1
0.1 - 10.0
-
0.1
1.0
Parameter C for customer programmable
curve for step 1
tPRCrv1
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer programmable
curve for step 1
tTRCrv1
0.005 - 100.000
-
0.001
13.500
Parameter TR for customer programmable
curve for step 1
tCRCrv1
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer programmable
curve for step 1
HarmBlock1
Disabled
Enabled
-
-
Disabled
Enable block of step 1 for harmonic restraint
I2>Min
5 - 2500
%IB
1
5
Minimum used operating phase current level
for step 2 in % of IBase, if I2> is less than
I2>Min then I2> is set to I2>Min
I2>Max
5 - 2500
%IB
1
2500
Maximum used operating phase current level
for step 2 in % of IBase, if I2> is greater than
I2>Max then I2> is set to I2>Max
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for step 2
tReset2
0.000 - 60.000
s
0.001
0.020
Constant reset time for step 2
tPCrv2
0.005 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 2
tACrv2
0.005 - 200.000
-
0.001
13.500
Parameter A for customer programmable
curve for step 2
Table continues on next page
Section 8
1MRK 511 408-UUS A
Current protection
176
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...