Section 20
Remote communication
20.1
Binary signal transfer
IP12423-1 v2
20.1.1
Identification
M14849-1 v3
Function description
IEC 61850 identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Binary signal transfer,
receive
BinSignRec1_1
BinSignRec1_2
BinSignReceive2
-
-
Binary signal transfer, 2Mbit
receive
BinSigRec1_12M
BinSigRec1_22M
-
-
Binary signal transfer,
transmit
BinSignTrans1_1
BinSignTrans1_2
BinSignTransm2
-
-
Binary signal transfer, 2Mbit
transmit
BinSigTran1_12M
BinSigTran1_22M
-
-
20.1.2
Functionality
SEMOD52522-4 v7
The remote end data communication is used for the transmission of analog values for
line differential protection or for the transmission of only binary signals between IEDs.
The binary signals are freely configurable and can thus be used for any purpose, such
as communication scheme related signals, transfer trip and/or other binary signals
between IEDs.
Communication between two IEDs requires that each IED is equipped with a Line
Data Communication Module (LCDM). The LDCM then acts as an interface to 64
kbit/s and 2Mbit/s communication channels for duplex communication between the
IEDs. In 2Mbit/s mode, each LDCM can send and receive up to 9 analog and up to 192
binary signals simultaneously. In 64kbit/s mode, the LDCM can be configured to work
in either analog mode or binary mode. In analog mode, the IED can send and receive
up to 3 analog signals and up to 8 binary signals. In binary mode, the LDCM can send
and receive only binary data (up to 192 binary signals).
1MRK 511 408-UUS A
Section 20
Remote communication
Phasor measurement unit RES670 2.2 ANSI
727
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...