![ABB Relion RES670 Скачать руководство пользователя страница 403](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485403.webp)
14.5.6
Operation principle
SEMOD158597-4 v5
AutomationBits function (AUTOBITS) has 32 individual outputs which each can be
mapped as a Binary Output point in DNP3. The output is operated by a "Object 12" in
DNP3. This object contains parameters for control-code, count, on-time and off-time.
To operate an AUTOBITS output point, send a control-code of latch-On, latch-Off,
pulse-On, pulse-Off, Trip or Close. The remaining parameters will be regarded were
appropriate. ex: pulse-On, on-time=100, off-time=300, count=5 would give 5 positive
100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in the
same way the setting
Operation
:
Enabled/Disabled
does. That means that, upon
activation of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The
BLOCK acts like an overriding, the function still receives data from the DNP3 master.
Upon deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3
master again, momentarily. For AUTOBITS , the PSTO input determines the operator
place. The command can be written to the block while in “Remote”. If PSTO is in
“Local” then no change is applied to the outputs.
14.6
Single command, 16 signals SINGLECMD
SEMOD119849-1 v2
14.6.1
Identification
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single command, 16 signals
SINGLECMD
-
-
14.6.2
Functionality
M12446-6 v5
The IEDs can receive commands either from a substation automation system or from
the local HMI. The command function block has outputs that can be used, for example,
to control high voltage apparatuses or for other user defined functionality.
1MRK 511 408-UUS A
Section 14
Control
Phasor measurement unit RES670 2.2 ANSI
397
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...