22.2.4
Settings
IP11026-1 v2
PID-3572-SETTINGS v5
Table 599:
SETGRPS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ActiveSetGrp
SettingGroup1
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6
-
-
SettingGroup1
Active setting group
MaxNoSetGrp
1 - 6
-
1
1
Max number of setting groups 1-6
22.2.5
Operation principle
M12008-6 v3
M12008-8 v11
Parameter setting groups ActiveGroup function has six functional inputs, each
corresponding to one of the setting groups stored in the IED. Activation of any of these
inputs changes the active setting group. Eight functional output signals are available
for configuration purposes, so that information on the active setting group is always
available.
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ActiveGroup function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower order
setting group has priority. This means that if for example both group four and group
two are set to be activated, group two will be the one activated.
Every time a setting is changed, the output signal GRP_CHGD is sending a pulse.
Activating or deactivating test mode is made by changing a parameter, consequently
this will also cause a pulse on the GRP_CHGD output.
The parameter
MaxNoSetGrp
defines the maximum number of setting groups in use to
switch between.
The output
REMSETEN
indicates whether setting changes over IEC 61850 are enabled
or not. Per default, this is not enabled, which results in
REMSETEN
being at a logical
low level. If setting changes via IEC 61850 are enabled, then
REMSETEN
will be a
1MRK 511 408-UUS A
Section 22
Basic IED functions
Phasor measurement unit RES670 2.2 ANSI
775
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...