Time Accumulation
Transgression Supervision
Plus Retain
BLOCK
ACC_HOUR
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC15000322.vsd
Loop Delay
Loop Delay
tWarning
ACC_DAY
ADDTIME
tAddToTime
IEC15000322 V1 EN-US
Figure 236:
TEILGAPC Simplified logic
TEILGAPC main functionalities
•
IN: Accumulation of the elapsed time when input IN is high
•
applicable to very long time accumulation (≤
99999.9
hours)
•
output
ACC_HOUR
presents accumulated value in hours and
ACC_DAY
presents accumulated value in days
•
accumulated value is retained in a non-volatile memory
•
any retained value is used as initiation value for the integration following by
a restart
•
RESET: Reset of the accumulated value. Consequently all other outputs are also
reset
•
independent of the input
IN
value
•
reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input
IN
is high
during the reset.
•
reset can be made by activation of input
RESET
or from LHMI or with IEC
61850 command
•
ADDTIME: Manually add time to the currently accumulated time
Section 16
1MRK 511 408-UUS A
Monitoring
592
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...