![ABB Relion RES670 Скачать руководство пользователя страница 165](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485165.webp)
-1.5
-1
-0.5
0
0.5
1
1.5
-1
-0.5
0
0.5
1
1.5
-------
------
------
-----
-----
-----
-----
-----
---
--
---
-
--
--
-
--
--
--
--
--
--
--
--
---
---
---
---
---
---
---
---
----
----
----
----
------
Real part (R) of Z in Ohms
Im
a
g
in
a
ry
p
a
rt
(
X
)
o
f Z
in
O
h
m
s
^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^ ^
-
-
--
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
--
-
-
-
-
--
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
--
-
-
0
1
Zone 1
Zone 2
The 1st
pole slip
occurred
relay
X in Ohms
The 2nd
pole slip
occurred
R in Ohms
RE
SE
2
3
to the 3rd
pole-slip
¬
trajectory
of Z(R, X)
Pre-disturbance
normal load
Z(R, X)
0
®
pre-disturbance Z(R, X)
1
®
Z(R, X) under 3-phase fault
2
®
Z(R, X) when fault cleared
3
®
Z when pole-slip declared
lens determined
®
by the setting
Pickup Angle = 120°
limit of reach
®
ANSI10000109-1-en.vsd
ANSI10000109 V1 EN-US
Figure 42:
Loci of the complex impedance Z(R, X) for a typical case of generator
losing step after a short circuit that was not cleared fast enough
Under typical, normal load conditions, when the protected generator supplies the active
and the reactive power to the power system, the complex impedance Z(R, X) is in the
1st quadrant, point 0 in Figure
. One can see that under a three-phase fault
conditions, the centre of oscillation is at the point of fault, point 1, which is logical, as
all three voltages are zero or near zero at that point. Under the fault conditions the
generator accelerated and when the fault was finally cleared, the complex impedance
Z(R, X) jumped to the point 2. By that time, the generator has already lost its step,
Z(R, X) continues its way from the right-hand side to the left-hand side, and the 1st
pole-slip cannot be avoided. If the generator is not immediately disconnected, it will
continue pole-slipping — see Figure
, where two pole-slips (two pole-slip cycles)
are shown. Under out-of-step conditions, the centre of oscillation is where the locus of
the complex impedance Z(R, X) crosses the (impedance) line connecting the points SE
(Sending End), and RE (Receiving End). The point on the SE – RE line where the
trajectory of Z(R, X) crosses the impedance line can change with time and is mainly a
function of the internal induced voltages at both ends of the equivalent two-machine
system, that is, at points SE and RE.
Measurement of the magnitude, direction and rate-of-change of load impedance
relative to a generator’s terminals provides a convenient and generally reliable means
of detecting whether machines are out-of-step and pole-slipping is taking place.
Measurement of the rotor (power) angle δ is important as well.
1MRK 511 408-UUS A
Section 7
Impedance protection
Phasor measurement unit RES670 2.2 ANSI
159
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...