Name
Values (Range)
Unit
Step
Default
Description
RemModControl
Disabled
Maintenance
All levels
-
-
Disabled
Remote Mode Control
AllowSimulation
No
Yes
-
-
No
Allow simulated GOOSE values or simulated
sampled measured values
RemSetControlEd2
Disabled
Enabled
-
-
Disabled
Changing settings over 61850 enabled (only
for IEC61850 Ed2)
ResvTmsEd2
1 - 3600
s
1
60
Reservation time (only for IEC61850 Ed2)
19.4.4
Technical data
IP14434-1 v1
M15031-1 v8
Table 470:
Communication protocols
Function
Value
Protocol
IEC 61850-8-1
Communication speed for the IEDs
100BASE-FX
Protocol
IEC 60870–5–103
Communication speed for the IEDs
9600 or 19200 Bd
Protocol
DNP3.0
Communication speed for the IEDs
300–115200 Bd
Protocol
TCP/IP, Ethernet
Communication speed for the IEDs
100 Mbit/s
Protocol
LON
Communication speed for the IEDs
1.25 Mbit/s
Protocol
SPA
Communication speed for the IEDs
300–38400 Bd
19.4.5
Generic communication function for Single Point indication
SPGAPC, SP16GAPC
SEMOD55999-1 v4
19.4.5.1
Functionality
SEMOD55713-5 v8
Generic communication function for Single Point indication (SPGAPC) is used to send
one single logical signal to other systems or equipment in the substation.
Section 19
1MRK 511 408-UUS A
Station communication
628
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...