16.3.2
Functionality
GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v6
Insulation supervision for liquid medium (SSIML (71)) is used for monitoring the
transformer condition. Binary information based on the oil level in the transformer is
used as input signals to the function. In addition, the function generates alarms based
on received information.
16.3.3
Function block
GUID-AC82A86C-495D-4CBD-9BF9-3CC760591AA9 v3
SSIML (71)
BLOCK
BLKALM
SENLEVEL
SENTEMP
SENLVLALM
SENLEVELLO
SETLLO
SETTLO
RESETLO
LOCKOU T
LVLLO
TEMPLO
ALARM
LVLALM
TEMPALM
LEVEL
TEMP
ANSI09000128-2-en.vsdx
ANSI09000128 V2 EN-US
Figure 205:
SSIML (71) function block
16.3.4
Signals
GUID-0C378BB3-2104-417F-94B5-16EFC55151FE v2
PID-6951-INPUTSIGNALS v7
Table 404:
SSIML Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
BLKALM
BOOLEAN
0
Block all the alarms
SENLEVEL
REAL
0.0
Level input from CB
SENTEMP
REAL
0.0
Temperature of the insulation medium from CB
SENLVLALM
BOOLEAN
0
Level alarm signal
SENLVLLO
BOOLEAN
0
Level lockout signal
SETLLO
BOOLEAN
0
Set level lockout
SETTLO
BOOLEAN
0
Set temperature lockout
RESETLO
BOOLEAN
0
Reset level and temperature lockout
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
529
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...