15.15.4
Signals
PID-6836-INPUTSIGNALS v2
Table 349:
TEIGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the integration and block the other outputs
IN
BOOLEAN
0
The input signal that is used to measure the elapsed
time, when its value is high
RESET
BOOLEAN
0
Reset the integration time
PID-6836-OUTPUTSIGNALS v2
Table 350:
TEIGAPC Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the
warning limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the alarm
limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the
overflow limit
ACCTIME
REAL
Integrated elapsed time in seconds
15.15.5
Settings
PID-6836-SETTINGS v2
Table 351:
TEIGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
tWarning
1.00 - 999999.00
s
0.01
600.00
Time limit for warning supervision
tAlarm
1.00 - 999999.00
s
0.01
1200.00
Time limit for alarm supervision
15.15.6
Operation principle
GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3
The elapsed time integrator (TEIGAPC) provides
•
time integration, accumulating the elapsed time when a given binary signal has
been high
•
blocking and reset of the total integrated time
•
supervision of limit transgression and overflow, the overflow limit is fixed to
999999.9 seconds
•
retaining of the integrated value
1MRK 511 408-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.2 ANSI
477
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...