When EnaAbs
is set as absolute comparison and
SetValue
is set less
than 0.2% of the set unit then INLOW output will never pickups.
During the above mentioned condition, due to marginal value for
avoiding oscillations of function outputs, the INLOW output will never
set.
15.17.7
Technical data
GUID-62792FCB-B436-4034-9A08-C9FF918FF547 v1
REALCOMP function can compare the values from milli value level to giga value
level and the maximum expectable accuracy level from the function is 10 µ.
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v3
Table 362:
Number of REALCOMP instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
REALCOMP
10
10
10
Section 15
1MRK 511 408-UUS A
Logic
486
Phasor measurement unit RES670 2.2 ANSI
Technical manual