PID-3406-SETTINGS v5
Table 615:
SMAI2 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
-
-
InternalDFTRef
DFT reference
ConnectionType
Ph-N
Ph-Ph
-
-
Ph-N
Input connection type
AnalogInputType
Voltage
Current
-
-
Voltage
Analog input signal type
Table 616:
SMAI2 Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Negation
Disabled
NegateN
Negate3Ph
NeN
-
-
Disabled
Negation
MinValFreqMeas
5 - 200
%
1
10
Limit for frequency calculation in % of VBase
22.9.5
Operation principle
SEMOD55746-4 v13
Every Signal matrix for analog inputs function (SMAI) can receive four analog signals
(three phases and one neutral or residual value), either voltage or current, see
figure
. SMAI outputs give information about every aspect of the
3ph analog signals acquired (phase angle, RMS value, frequency and frequency
derivates etc. – 244 values in total). The BLOCK input will force all outputs to value
zero if BLOCK is TRUE (1).
System phase rotation and frequency are defined using the
PhaseRotation
and
Frequency
settings in the primary system values PRIMVAL function. Logic 1 in the
REVROT input to the SMAI function means that the phase rotation is changed relative
to the set
PhaseRotation
in PRIMVAL.
Section 22
1MRK 511 408-UUS A
Basic IED functions
790
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...