Vpickup
VBase kV
>
⋅
(%)
(
) /
3
EQUATION1610 V2 EN-US
(Equation 54)
and operation for phase-to-phase voltage over:
Vpickup
(%) VBase(kV)
>
×
EQUATION1992 V1 EN-US
(Equation 55)
When phase-to-ground voltage measurement is selected the function
automatically introduces division of the base value by the square root
of three.
9.2.7.1
Measurement principle
M15330-6 v6
All the three voltages are measured continuously, and compared with the set values,
Pickup1
for Step 1 and
Pickup2
for Step 2. The parameters
OpMode1
and
OpMode2
influence the requirements to activate the PICKUP outputs. Either
1 out of 3
,
2 out of 3
or
3 out of 3
measured voltages have to be higher than the corresponding set point to
issue the corresponding PICKUP signal.
To avoid oscillations of the output PICKUP signal, a hysteresis is included.
9.2.7.2
Time delay
M15330-10 v11
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (TOV). For the inverse time delay four different modes are available:
•
inverse curve A
•
inverse curve B
•
inverse curve C
•
customer programmable inverse curve
The type A curve is described as:
t
TD
V
Vpickup
Vpickup
=
−
>
>
EQUATION1625 V2 EN-US
(Equation 56)
1MRK 511 408-UUS A
Section 9
Voltage protection
Phasor measurement unit RES670 2.2 ANSI
291
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...