When definite time delay is selected the function will trip as shown in figure
.
Detailed information about individual stage reset/operation behavior is shown in figure
respectively. Note that by setting
tResetn
=
0.0s
, instantaneous reset of
the definite time delayed stage is ensured.
a<b
a
b
Pickup1
V
TRST1
PU_ST1
AND
0
t1
tReset1
0
R
ANSI09000785-3-en.vsd
ANSI09000785 V3 EN-US
Figure 91:
Logic diagram for step 1, DT operation
Pickup1
PU_ST1
TRST1
tReset1
t1
ANSI10000039-3-en.vsd
ANSI10000039 V3 EN-US
Figure 92:
Example for Definite Time Delay stage1 reset
1MRK 511 408-UUS A
Section 9
Voltage protection
Phasor measurement unit RES670 2.2 ANSI
281
Technical manual