Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each input signal.
Table 545:
INF
Description
TYP
GI
COT
64
Pickup phase A
2
Y
1,7,9
65
Pickup phase B
2
Y
1,7,9
66
Pickup phase C
2
Y
1,7,9
67
Pickup residual current IN
2
Y
1,7,9
68
Trip general
2
N
1,7
69
Trip phase A
2
N
1,7
70
Trip phase B
2
N
1,7
71
Trip phase C
2
N
1,7
72
Back up trip I>>
2
N
1,7
73
Fault location in ohm
4
N
1,7
74
Forward/line
2
N
1,7
75
Reverse/busbar
2
N
1,7
76
Signal transmitted
2
N
1,7
77
Signal received
2
N
1,7
78
Zone 1
2
N
1,7
79
Zone 2
2
N
1,7
80
Zone 3
2
N
1,7
81
Zone 4
2
N
1,7
82
Zone 5
2
N
1,7
84
Pickup general
2
Y
1,7,9
85
Breaker failure
2
N
1,7
86
Trip measuring system phase A
2
N
1,7
87
Trip measuring system phase B
2
N
1,7
88
Trip measuring system phase C
2
N
1,7
89
Trip measuring system neutral N
2
N
1,7
90
Over current trip, stage low
2
N
1,7
91
Over current trip, stage high
2
N
1,7
92
Ground-fault trip, stage low
2
N
1,7
93
Ground-fault trip, stage high
2
N
1,7
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
713
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...