GUID-E8D0EE7C-D7B8-46C3-9C0D-363FFC75DE93 v5
Table 182:
FTAQFVR (81A) technical data
Function
Range or value
Accuracy
Trip value, frequency high limit level at
symmetrical three phase voltage
(35.00 – 90.00) Hz
±2.0 mHz
Trip value, frequency low limit level at
symmetrical three phase voltage
(30.00 – 85.00) Hz
±2.0 mHz
Trip value, voltage high and low limit for
voltage band limit check
(0.0 – 200.0)% of VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Trip value, current pickup level
(5.0 – 100.0)% of IBase
±1.0% of I
r
or 0.01 A at I≤I
n
Independent time delay for the continuous
time limit at f
set
+0.02 Hz to f
set
-0.02 Hz
(0.0 – 6000.0) s
±0.2% or ±250 ms whichever is
greater
Independent time delay for the
accumulation time limit at f
set
+0.02 Hz to
f
set
-0.02 Hz
(10.0 – 90000.0) s
±0.2% or ±250 ms whichever is
greater
Section 10
1MRK 511 408-UUS A
Frequency protection
324
Phasor measurement unit RES670 2.2 ANSI
Technical manual