18.4.2
Settings
PID-6770-SETTINGS v2
Table 463:
MU1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SampleValueID
0 - 34
-
1
ABB_MU0101
Sample Value ID (SVID) for the merging unit
[0-34 char]
APConnection
None
AP1
AP2
AP3
AP4
-
-
None
Access point connection for the merging unit
PID-6850-SETTINGS v3
Table 464:
MU1_HW Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
18.4.3
Monitored data
PID-6850-MONITOREDDATA v3
Table 465:
MU1_HW Monitored data
Name
Type
Values (Range)
Unit
Description
MUDATA
BOOLEAN
0=Ok
1=Error
-
Fatal error, data not received,
transmission errors, time-
sync issues or inconsistent
sample rate
SYNCH
BOOLEAN
0=Ok
1=Error
-
Operational mode on
ethernet link
SMPLLOST
BOOLEAN
1=Yes
0=No
-
Fatal error or recovery state
after fatal error. High if any
subscribed channel has bad
quality or TEST while IED not
in test mode.
MUSYNCH
BOOLEAN
0=Ok
1=Error
-
MU not synced or MU clock
not synced to same clock as
IED
Table continues on next page
1MRK 511 408-UUS A
Section 18
Ethernet
Phasor measurement unit RES670 2.2 ANSI
617
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...