Name
Values (Range)
Unit
Step
Default
Description
QDbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
QZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
QHiHiLim
-2000.0 - 2000.0
%SB
0.1
150.0
High High limit in % of SBase
QHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
High limit in % of SBase
QLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
Low limit in % of SBase
QLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
Low Low limit in % of SBase
QLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
PFDbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
PFZeroDb
0 - 100000
m%
100
500
Magnitude zero point clamping in 0,001% of
range
PFHiHiLim
-1.000 - 1.000
-
0.001
1.000
High High limit (physical value)
PFHiLim
-1.000 - 1.000
-
0.001
0.800
High limit (physical value)
PFLowLim
-1.000 - 1.000
-
0.001
-0.800
Low limit (physical value)
PFLowLowLim
-1.000 - 1.000
-
0.001
-1.000
Low Low limit (physical value)
PFLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
VDbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
VZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
VHiHiLim
0.0 - 200.0
%VB
0.1
150.0
High High limit in % of UBase
VHiLim
0.0 - 200.0
%VB
0.1
120.0
High limit in % of VBase
VLowLim
0.0 - 200.0
%VB
0.1
80.0
Low limit in % of VBase
VLowLowLim
0.0 - 200.0
%VB
0.1
60.0
Low Low limit in % of VBase
VLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
IDbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
IZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in 0,001% of
range
IHiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IHiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
ILowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
ILowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
ILimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common for
all limits
Table continues on next page
Section 16
1MRK 511 408-UUS A
Monitoring
498
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...