19.7.5.3
Function block
GUID-25B47484-2976-4063-BD81-AE02D03B08B0 v1
IEC10000290-1-en.vsd
I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290 V1 EN-US
Figure 271:
I103EF function block
19.7.5.4
Signals
PID-3974-INPUTSIGNALS v5
Table 511:
I103EF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
51_EFFW
BOOLEAN
0
Information number 51, ground-fault forward
52_EFREV
BOOLEAN
0
Information number 52, ground-fault reverse
19.7.5.5
Settings
PID-3974-SETTINGS v5
Table 512:
I103EF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
160
Function type (1-255)
19.7.6
Function status fault protection for IEC 60870-5-103
I103FLTPROT
19.7.6.1
Functionality
GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For example: 68_TRGEN represents
the General Trip of the device, and therefore must be connected to the general trip
signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
691
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...