Name
Values (Range)
Unit
Step
Default
Description
tPCrv3
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 3
tACrv3
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 3
tBCrv3
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 3
tCCrv3
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 3
tPRCrv3
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 3
tTRCrv3
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 3
tCRCrv3
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset time
curve for step 3
IN4>Min
1 - 2500
%IB
1
1
Minimum used operate residual current level
for step 4 in % of IBase, if IN4> is less than
IN4>Min then IN4> is set to IN4>Min
IN4>Max
1 - 2500
%IB
1
2500
Maximum used operate residual current level
for step 4 in % of IBase, if IN4> is greater
than IN4>Max then IN4> is set to IN4>Max
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step4 (Instantaneous /
IEC / ANSI)
tReset4
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 4
tPCrv4
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 4
tACrv4
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 4
tBCrv4
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 4
tCCrv4
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 4
tPRCrv4
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 4
tTRCrv4
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 4
tCRCrv4
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset time
curve for step 4
1MRK 511 408-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.2 ANSI
197
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...