19.4.12.4
Operation principle
GUID-950F2501-9183-43C0-A193-7D15124F6CCE v1
The DVALIDx output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value
Data Valid
Comm Valid
Test
Incoming data with q=Normal
Updated
1
1
0
Incoming data with q=oldData
0
0
1
0
Incoming data with q=Invalid
0
0
1
0
Incoming data with q=test
0
0
1
1
Incoming data with q=test+oldData
0
0
1
1
Receiver in block
0
0
1
0
Receiver in block and communication
error
0
0
0
0
Receiver in test mode and incoming
data with q= Normal
Updated
1
1
0
Receiver in test mode and incoming
data with q= Test
Updated
1
1
1
Communication Error
0
0
0
0
At least one of the inputs of this GOOSE block must be linked either in
SMT by means of a cross or in ACT by means of a GOOSE connection
(if easy GOOSE engineering is enabled) to receive any data. Only those
outputs whose source input is linked/connected will be updated.
The implementation for IEC 61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DVALIDx
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DVALIDx output will be LOW.
1MRK 511 408-UUS A
Section 19
Station communication
Phasor measurement unit RES670 2.2 ANSI
651
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...