Disturbance report
Record no. N
Record no. N+1
Record no. N+100
General dist.
Information & Setting
infotrmation
Indications
Trip
values
Event
recordings
Disturbance
recording
Event list
(SOE)
ANSI05000161-2-en.vsdx
ANSI05000161 V2 EN-US
Figure 224:
Disturbance report structure
Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded
when the memory is full, the oldest disturbance report is overwritten by the new one.
The total recording capacity for the disturbance recorder is depending of sampling
frequency, number of analog and binary channels and recording time and settings
information. Figure
shows the number of recordings versus the total recording
time tested for a typical configuration, that is, in a 60 Hz system it is possible to record
80 where the average recording time is 3.4 seconds. The memory limit does not affect
the rest of the disturbance report (Event list (EL), Event recorder (ER), Indications
(IND) and Trip value recorder (TVR)).
100
400 s
350
300
40
60
80
40 analog
96 binary
20 analog
96 binary
3.4s
6.3s
6.3s
60 Hz
50 Hz
6.3s
3.4s
250
Total recording time
Number of recordings
en05000488_ansi.vsd
ANSI05000488 V1 EN-US
Figure 225:
Example of number of recordings versus the total recording time
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
573
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...