en05000132_ansi.vsd
51
51
A1
B1
Feeder
Time axis
t=0
t=t
1
t=t
2
t=t
3
ANSI05000132 V1 EN-US
Figure 345:
Selectivity steps for a fault on feeder B1
where:
t=0
is The fault occurs
t=t
1
is Protection B1 trips
t=t
2
is Breaker at B1 opens
t=t
3
is Protection A1 resets
In the case protection B1 shall trip without any intentional delay (instantaneous). When
the fault occurs the protections pickup to detect the fault current. After the time t
1
the
protection B1 send a trip signal to the circuit breaker. The protection A1 starts its delay
timer at the same time, with some deviation in time due to differences between the two
protections. There is a possibility that A1 will pickup before the trip is sent to the B1
circuit breaker. At the time t
2
the circuit breaker B1 has opened its primary contacts
and thus the fault current is interrupted. The breaker time (t2 - t1) can differ between
different faults. The maximum opening time can be given from manuals and test
protocols. Still at t
2
the timer of protection A1 is active. At time t
3
the protection A1 is
reset, that is the timer is stopped.
In most applications it is required that the times shall reset as fast as possible when the
current fed to the protection drops below the set current level, the reset time shall be
minimized. In some applications it is however beneficial to have some type of delayed
reset time of the overcurrent function. This can be the case in the following
applications:
1MRK 511 408-UUS A
Section 26
Inverse time characteristics
Phasor measurement unit RES670 2.2 ANSI
881
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...