19.7.8.3
Function block
GUID-69C2C974-2D64-4174-9F9A-15383C09050D v1
IEC10000293-1-en.vsd
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293 V1 EN-US
Figure 274:
I103SUPERV function block
19.7.8.4
Signals
PID-3976-INPUTSIGNALS v5
Table 517:
I103SUPERV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
32_MEASI
BOOLEAN
0
Information number 32, measurand supervision of I
33_MEASU
BOOLEAN
0
Information number 33, measurand supervision of V
37_IBKUP
BOOLEAN
0
Information number 37, I high-high back-up protection
38_VTFF
BOOLEAN
0
Information number 38, fuse failure VT
46_GRWA
BOOLEAN
0
Information number 46, group warning
47_GRAL
BOOLEAN
0
Information number 47, group alarm
19.7.8.5
Settings
PID-3976-SETTINGS v5
Table 518:
I103SUPERV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
19.7.9
Status for user defined signals for IEC 60870-5-103
I103USRDEF
19.7.9.1
Functionality
GUID-DADC9CE4-2E80-426C-A3B6-A8E8C7AC3CD4 v3
I103USRDEF is a function block with user defined input signals in monitor direction.
Each instance is associated with a Function Type (FUN) and each input signal with an
Section 19
1MRK 511 408-UUS A
Station communication
696
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...