![ABB Relion RES670 Скачать руководство пользователя страница 814](http://html.mh-extra.com/html/abb/relion-res670/relion-res670_technical-manual_4485814.webp)
23.2.4
Local human-machine interface (Local HMI)
SEMOD56218-5 v4
Refer to section
for information.
23.2.5
Transformer input module (TRM)
IP15581-1 v1
23.2.5.1
Introduction
M14875-3 v9
The transformer input module is used to galvanically separate and adapt the secondary
currents and voltages generated by the measuring transformers. The module has twelve
inputs in different combinations of currents and voltage inputs.
Alternative connectors of Ring lug or Compression type can be ordered.
23.2.5.2
Design
M14858-3 v7
The transformer module has 12 input transformers. There are several versions of the
module, each with a different combination of voltage and current input transformers.
Basic versions:
•
6 current channels and 6 voltage channels
•
7 current channels and 5 voltage channels
•
9 current channels and 3 voltage channels
•
12 current channels
•
6 current channels
•
10 current channels and 2 voltage channels
The rated values and channel type, measurement or protection, of the current inputs are
selected at order.
Transformer input module for measuring should not be used with
current transformers intended for protection purposes, due to
limitations in overload characteristics.
The TRM is connected to the ADM and NUM.
For configuration of the input and output signals, refer to section
Section 23
1MRK 511 408-UUS A
IED hardware
808
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...