Voltage
Time
HystAbs1
PICKUP
TRIP
PICKUP1
PICKUP
TRIP
t
tIReset1
Time
Time
Integrator
t
Frozen Timer
Linearly
decreased
Instantaneous
Measured
Voltage
tIReset1
ANSI05000010-3-en.vsd
ANSI05000010 V3 EN-US
Figure 89:
Voltage profile not causing a reset of the pickup signal for step 1, and inverse time delay at different
reset types
1MRK 511 408-UUS A
Section 9
Voltage protection
Phasor measurement unit RES670 2.2 ANSI
279
Technical manual