3.7
Technical data
SEMOD55412-1 v1
M16988-1 v11
Table 27:
TRM - Energizing quantities, rated values and limits for protection transformer
Description
Value
Frequency
Rated frequency f
r
50/60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
1 or 5 A
Operating range
(0-100) x I
r
Thermal withstand
100 × I
r
for 1 s *)
30 × I
r
for 10 s
10 × I
r
for 1 min
4 × I
r
continuously
Dynamic withstand
250 × I
r
one half wave
Burden
< 20 mVA at I
r
= 1 A
< 150 mVA at I
r
= 5 A
*) max. 350 A for 1 s when COMBITEST test switch is included.
Voltage inputs **)
Rated voltage U
r
110 or 220 V
Operating range
0 - 340 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
Table 28:
TRM - Energizing quantities, rated values and limits for measuring transformer
Description
Value
Frequency
Rated frequency f
r
50/60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
1A
5 A
Operating range
(0-1.8) × I
r
(0-1.6) × I
r
Table continues on next page
1MRK 511 408-UUS A
Section 3
Analog inputs
Phasor measurement unit RES670 2.2 ANSI
71
Technical manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Страница 2: ......
Страница 276: ...270 ...
Страница 306: ...300 ...
Страница 360: ...354 ...
Страница 406: ...400 ...
Страница 614: ...608 ...
Страница 732: ...726 ...
Страница 748: ...742 ...
Страница 884: ...878 ...
Страница 932: ...926 ...
Страница 933: ...927 ...