8
vacon • 98
PROFINET IO
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
* 12 and 16 process data items are available in VACON
®
NXP AC Drive. See Chapter 16 "Appendix 6 -
Fieldbus option board communication".
* See Chapter 8.3.1 "Choosing telegram type".
Control and Status Word monitoring values
When using this telegram, monitoring values contains values as shown in table below.
8.3.2.3
VACON® specific Telegram 2 and its variants
These telegrams (Table 55) use VACON
®
defined control word, status word, speed setpoint value
and speed actual value to directly access the AC drive application. The difference to vendor telegram
1 types are the added general control and status words.
NOTE!
This telegram type is not supported when using VACON
®
100 family AC drives. 32-bit process
data support for VACON
®
100 family AC drives is added in future release.
141
Vendor Telegram 1 + 16 Process Data *
Vendor 1 + 16 PD
Table 53. Vendor telegram 1 setpoint and actual data
Bytes
Setpoint
Actual value
1...2
FB FIXED CW
FB FIXED SW
3...4
FB SPEED REF
FB SPEED ACT
5...6
PDI1
PDO1
7...8
PDI2
PDO2
...
...
....
19...20
PDI8
PDO8
21...22
PDI9*
PDO9*
...
...
...
35...36
PDI16*
PDO16*
Table 54. Control and Status Word monitoring values
Name
Value
Drive CW
FBFixedControlWord
Drive SW
FBFixedStatusWord
Protocol CW
FBFixedControlWord
Protocol SW
FBFixedStatusWord
Table 55. Vendor telegram 2 and variants
Telegram No.
Telegram
Abbreviation
117
Vendor Telegram 2
Vendor 2
118
Vendor Telegram 2 + 1 Process Data
Vendor 2 + 1 PD
119
Vendor Telegram 2 + 2 Process Data
Vendor 2 + 2 PD
120
Vendor Telegram 2 + 3 Process Data
Vendor 2 + 3 PD
121
Vendor Telegram 2 + 4 Process Data
Vendor 2 + 4 PD
Table 52. Vendor telegram 1 and variants
Telegram No.
Telegram
Abbreviation
Summary of Contents for optea
Page 2: ......