APPENDIX 4 - FIELDBUS PARAMETRISATION
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
14.
APPENDIX 4 - FIELDBUS PARAMETRISATION
The following chapter describes briefly how to parametrize the AC drive in order for the motor to be
controllable via fieldbus. These instructions are written for basic applications. For more
information, consult the application-specific manual.
In order for the AC drive to accept commands from the fieldbus network, the control place of the AC
drive has to be set to fieldbus. The default value of the parameter "Control Place" is usually I/O. Note
that if the control unit firmware is updated, the default settings are restored. In addition, some
applications may have the remote speed reference selection set by default to other than fieldbus. In
these cases, the speed reference selection must be set to fieldbus, in order for the speed reference
to be controlled via fieldbus.
NOTE!
The motor control mode should be selected to support the used process and profile.
14.1
Fieldbus control and basic reference selection
The following tables list some of the parameters related to fieldbus control in case of VACON
®
applications for the VACON
®
100 family, VACON
®
20 / 20X and VACON
®
NXP. See the application
specific manuals for more detailed information.
Parameters can be read and written by using the drive panel, PC Tools or fieldbus protocol. The
table below contains links to chapters where the ID value reading is described.
Table 222. Parametrization for VACON
®
20 (standard application)
Table 220. Links to ID value descriptions
Protocol
Chapter
Modbus
See Chapter "7.3.2.5.1. VACON® application IDs"
See Chapter "7.3.2.5.4. ID map"
Profinet IO
See Chapter 8.4.7 "Drive parameter access using application ID"
EtherNet/IP
See Chapter 9.2.2.1 "Vendor Parameters Object, Class 0xA0"
Table 221. Parametrization for VACON
®
100 family (standard application)
Parameter name
ID
Value
Default
Panel Tree
Control mode
600
0 = Frequency
1 = Speed
2 = Torque
0
P 3.1.2.1
Remote control place
172
1 = Fieldbus CTRL
0
P 3.2.1
Local / remote
211
0 = Remote
0
P 3.2.2
Fieldbus ref. sel.
122
3 = Fieldbus
3
P 3.3.1.10
Controlling fieldbus
2539
-
1
P5.13.1
Parameter name
ID
Value
Default
Panel Tree
Motor control mode
600
0 = Frequency
1 = Speed
0
P 1.8
Rem. Control place 1
sel.
172
1 = Fieldbus CTRL
0
P 2.1
Local / remote
211
0 = Remote
0
P 2.5