PROFINET IO
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
The following table contains messages sent during writing values to ID 103 and ID 104.
Answer indicates a successful operation.
Attribute
0x10 = Value
No. of elements
0x01
Parameter Number
0x2711 (10001d)
Subindex
0x0067 (103d, ID 103)
Attribute
0x10 = Value
No. of elements
0x01
Parameter Number
0x2711 (10001d)
Subindex
0x0068 (104d, ID 104)
Parameter datatype
0x42 = WORD
Number of parameters
0x01
Value
0x0028 (Value for ID 103)
Parameter datatype
0x42 = WORD
Number of parameters
0x01
Value
0x0028 (Value for ID 104)
Table 99. Messages sent and received during writing value to ID 103
Message
Operation
Data
1
Write request
Request header
0x06 0x02 0x01 0x02
Parameter address
0x10 0x01 0x27 0x11 0x00 0x67
0x10 0x01 0x27 0x11 0x00 0x68
Parameter value
0x42 0x01 0x00 0x28
0x42 0x01 0x00 0x28
2
Write request response from AC drive to PLC
-
PLC waits until AC drive has finished processing the requested operation
3
PLC sends read request
4
Read request
response
Response header
0x06 0x02 0x01 0x01
Table 98. Request to write the value of parameter ID 103 and ID 104
Field
Contents