APPENDIX 1 - VACON® IO DATA DESCRIPTION
vacon • 211
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
11
11.8
FIELDBUS PROCESS DATA MAPPING AND SCALING
This chapter describes how standard applications map process data out items by default. For
further details, see the AC drive's Application Manua, especially when not using standard
application.
Table 213. Process data output mapping defaults for VACON
®
100 family
*Scaling is based on drive nominal power. Scaling can be seen from Table 217.
Table 214. Process data output mapping defaults for VACON
®
NXP (standard applications)
Table 215. Process data output mapping defaults for VACON
®
20 X/CP (standard applications)
*Scaling is based on drive nominal power. Scaling can be seen from Table 217.
PD Out
Mapped Application Data
ID
Unit
Scale
1
Output frequency
1
Hz
0.01 Hz
2
Motor speed
2
rpm
1 rpm
3
Motor current
3
A
Varies*
4
Motor torque
4
%
0.1%
5
Motor power
5
%
0.1%
6
Motor voltage
6
V
0.1 V
7
DC link voltage
7
V
1 V
8
Last active fault code
37
-
-
PD Out
Mapped Application Data
ID
Unit
Scale
1
Output frequency
1
Hz
0.01 Hz
2
Motor speed
2
rpm
1 rpm
3
Motor current
45
A
0.1 A
4
Motor torque
4
%
0.1%
5
Motor power
5
%
0.1%
6
Motor voltage
6
V
0.1 V
7
DC link voltage
7
V
1 V
8
Last active fault code
37
-
-
PD Out
Mapped Application Data
ID
Unit
Scale
1
Output frequency
1
Hz
0.01 Hz
2
Motor speed
2
rpm
1 rpm
3
Motor current
3
A
Varies*
4
Motor torque
4
%
0.1%
5
Motor power
5
%
0.1%
6
Motor voltage
6
V
0.1 V
7
DC link voltage
7
V
1 V
8
Last active fault code
37
-
-