PROFIdrive 4.1 state machine
STW1 (Control Word) and ZSW1 (Status Word) follow the state machine presented below:
Figure 39. General state diagram
NOTE!
When using VACON
®
NX series AC drives and option board in "PROFIdrive" mode, the stop
command always follows the configured stop mode and not the stop command given from fieldbus.
NOTE!
Quick stop only occurs if the application supports it. If the application does not support Quick
stop, a normal ramp stop is executed.
Table 48. PROFIdrive state machine commands
#
Bits of control word
Value
(hex)
Action(s)
VACON
®
100
family &
VACON
®
20X/CP
VACON
®
20 VACON
®
NXP
0
-
-
Self-initiation is performed
1
OFF AND No Coast Stop AND No
Quick Stop
STW1 bit 0 = False; 1, 2 = True
0x47E
None, requires that Drive is READY (ZSW1 sta-
tus word bit 13)
2
Coast Stop OR Quick Stop
STW1 bit 1 = False OR bit 2 = False
None
3
ON
STW1 bit 0 = True
0x477
None
4
Coast Stop OR Quick Stop
None
Highest priority transition
..
..
Lowest priority transition
15
11
13
12
9
8
14
1
6
10
4
7
3
5
2
0
Power ON
S1: Switching On Inhibited
ZSW1 bit 6 = True; 0,1,2 = False
General state diagram
11610A_uk
S2: Ready For Switching On
ZSW1 bit 0 = True; 1,2,6 = False
Ramp stop
Quick stop
S5: Switching Off
ZSW1 bit0,1 =True
bit 2,6=False
S3: Switched On
ZSW1 bit 0,1 = True; 2,6 = False
S4: Operation
ZSW1 bit 0,1,2 = True; 6=False