9
vacon • 180
EtherNet/IP
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
The status word bits are mapped to the object data according the following table.
The process data IN is mapped according to the following table.
The process data OUT is mapped according to the following table.
The Speed Reference is updated to the drive only when the NetRef bit is set to 1. The torque
reference is updated to the drive only when the motor control mode is “Torque Control”.
4
-
-
-
-
5
NetCtrl
Control Supervisor Object
NetCtrl
5
d
6
NetRef
AC/DC Drive Object
NetRef
4
d
7
NetProc
AC/DC Drive Object
NetProc
5
d
Table 156. CIP Status Word Mapping to Object Data
Bit
Bit name
Object
Attribute name
Attribute ID
0
Faulted
Control Supervisor Object
Faulted
10
d
1
Warning
Control Supervisor Object
Warning
11
d
2
Running1
Control Supervisor Object
Running1
7
d
3
Running2
Control Supervisor Object
Running2
8
d
4
Ready
Control Supervisor Object
Ready
9
d
5
CtrlFromNet
Control Supervisor Object
CtrlFromNet
15
d
6
RefFromNet
AC/DC Drive Object
RefFromNet
29
d
7
AtReference
AC/DC Drive Object
AtReference
3
d
Table 157. Process Data IN Mapping To Object Data
Parameter name
Object
Attribute name
Attribute ID
Speed Reference
AC/DC Drive Object
SpeedRef
8
d
Torque Reference
AC/DC Drive Object
TorqueRef
(ProcessDataIn1)
12
d
Process Reference
AC/DC Drive Object
ProcessRef
If Drive Mode is:
0 = ProcessDataIn1
4 = ProcessDataIn2
14
d
Drive Mode
AC/DC Drive Object
DriveMode
6
d
Table 158. Process Data OUT Mapping To Object Data
Parameter name
Object
Attribute name
Attribute ID
Speed Actual
AC/DC Drive Object
SpeedActual
7
d
Torque Actual
AC/DC Drive Object
TorqueActual
11
d
Process Actual
AC/DC Drive Object
ProcessActual
(ProcessDataOut1)
13
d
Drive State
Control Supervisor Object
State
6
d
Table 155. CIP Control Word Mapping To Object Data
Bit
Bit name
Object
Attribute name
Attribute ID